  • What affects the service life of the cooling tower

    Description of square counter flow FRP cooling tower:
    1. Standard design conditions: dry bulb temperature 31.5 ℃, wet bulb temperature 28 ℃, atmospheric pressure 99400pa, inlet water temperature 42 ℃, outlet water temperature 32 ℃;
    2. The special packing for inclined trapezoidal wave square tower is selected, which has excellent thermal performance and low ventilation resistance, so that this kind of cooling tower can achieve the design purpose of compact structure and small floor area;
    3.The structure is stable, and the tower top is provided with an overhaul platform, which makes maintenance and overhaul more convenient;
     
    faq09
     
    The wing type Vierendeel structure, large diameter, large area, low speed and low dynamic pressure FRP fan blades are adopted. The use of this kind of cooling tower has the characteristics of energy saving and low noise; Trough water distribution system is adopted, which is uniform and not easy to be blocked; The drenching filler is provided with a honeycomb water collector, which has good water collection effect and reduces the floating water loss of the cooling tower; The structure is simple, the operation weight is low, and the maintenance platform is set on the top of the tower, which is more convenient for maintenance. What to do to increase the service life of the square cooling tower: cleaning, maintenance and replacement of FRP cooling tower, maintenance and replacement of fan, motor and reducer, static balance adjustment of fan, maintenance and replacement of water distributor and water pipe, etc; Structural transformation of cooling tower, increase of thermal performance of cooling tower, tower noise, vibration control and other services; Improve the service life of the integral cooling tower; The cooling tower stops working. Before operation, we should carefully clean the dirt of the pipeline, the appearance of the water collector, packing box, water pool and other equipment to avoid blockage. Before putting the cooling tower into operation, it should be put into trial operation.
     
    faq10

    For the anti-corrosion treatment of cooling tower, due to the quality of water and the quality of some manufacturers, a large number of metal structures of cooling tower rust in a short time, which greatly shortens the service life. If they are not treated in time, they will undoubtedly be scrapped in advance. Some lubricating grease should be added to the automatic lubrication system, especially some high-temperature or large towers.
     
  • How to use the cooling tower correctly

    1. Preparation before operation: the cooling tower shall be inspected and cleaned before operation. The operation part shall be checked in detail and can be carried out only after there is no problem. The following are the areas to be checked:
    (1) Clean the sundries and sludge on the bottom basin and check whether the pipeline is blocked.
    (2) Wash the heat dissipation film and the soil in the bottom basin with high-pressure water (the water pressure should not be too high), and discharge the sewage through the sewage outlet
    (3) Check whether the motor wiring is correct and firm, and whether the motor junction box is tightly covered to avoid water and gas infiltration
    (4) Check the belt tightness in the belt drive
    (5) Check whether the fan rotates flexibly and smoothly, and whether the clearance between the tail of each fan blade and the shell of the water tower is uniform
    (6) Check whether the float valve assembly is properly installed
    (7) Check whether the number and density of each layer of film are appropriate
    (8) Check that all bolts of the cooling tower are tightened
     
    faq08

    2. Operation of cooling tower
    (1) Water level adjustment: fill the water basin and water pipe of the cooling tower to the operating water level first, and adjust the float valve combination to the operating water level to ensure that the water level of the bottom basin is still at the operating water level after the water pump is started, that is, 15mm below the overflow.
    (2) Turn on the motor switch and observe it from the top of the water tower. The fan should rotate clockwise and the air flow is drawn out from the top of the water tower. Start the circulating water system and check the operating current at this time. The current value does not exceed 95% of the rated current shown on the motor nameplate. After the water pump runs, it enters the rotating water sowing system through the central roar pipe and is distributed on the water sowing pipe Drench the water evenly and carefully.
     
    faq07

  • The role of cooling tower guide air duct

    The air duct of the cooling tower has four major functions: one is the maintenance structure of the fan; The second is the guarantee structure of air volume and air pressure; Third, ensure that hot and humid air is sent into the atmosphere, reduce backflow and improve the efficiency of the cynical tower workbench; The last function is to isolate the noise propagation path and damp the noise reduction function of consuming sound energy.

    faq05

    The air duct of the early cooling tower was a low air duct with right angle suction, which is still used by many manufacturers. Its disadvantages are large ventilation resistance and large kinetic energy consumption; The second generation air duct is a diffusion cylinder kinetic energy recovery air duct with an inclination of 11.5 degrees, and the suction inlet adopts streamlined design A diffusion section is added above the rotating surface of the fan blade, which can reduce the wind speed at the air outlet and reduce the dynamic pressure of hot and humid air entering the atmosphere, that is, reduce the total pressure of the fan and reduce the energy input.
     
    faq06
     
  • What are the structural characteristics of cooling tower products?

    As a professional cooling tower manufacturer, what are the structural characteristics of our professional high-quality cooling tower? Next, our professionals will give you a brief explanation. I believe it will be helpful for you to understand the products.   

    faq03
     
    1. Reliable cooling tower: the unique and rational design of the external turbine is installed outside the air duct of the cooling tower, which is convenient for maintenance. The structure is the same as that of the traditional cooling tower motor and reducer. The mechanical noise and failure rate of the traditional motor are eliminated, and the operation is stable and reliable.
    2. Cooling effect guarantee of cooling tower: the cooling system will change with the change of season. Three brake valves are specially designed for the external turbine, so that the fan speed increases or decreases with the increase or decrease of circulating water flow, and the air volume also increases or decreases, so as to stabilize the air-water ratio of the cooling tower in a better state and achieve better operation effect.
    3. Cooling tower environmental protection: after the external turbine replaces the motor, it reduces mechanical noise and vibration and reduces user energy.
     
     
    faq04

  • The benefits of regular replacement and cleaning of cooling tower packing

    The cooling tower packing shall be replaced regularly to ensure the normal working efficiency of the cooling tower. There has been aging for a long time, and some packing has fallen off, resulting in the decline of the heat exchange capacity of the cooling tower, affecting the operation efficiency of the refrigeration unit and consuming a lot of energy.

    faq01
     
    The crushed cooling tower packing enters the condenser copper pipe of the unit with the operation of the cooling water pump, and the cooling water treatment agent is added, which has the function of stripping rust. In case of uneven water distribution during the operation of the cooling tower, try to eliminate the causes in time, which are generally caused by the blockage of the water distribution pipe and the falling off of the nozzle. The dirt accumulated in the cooling pool and cooling tower packing shall be removed in time. Generally, it shall be cleaned every time it is out of service. When algae growth is found in the circulating water, impact chlorination shall be carried out to ensure that the residual chlorine in the water is 4mg / L or bleach for a short time. The turbidity and quantity of inlet and outlet water of FRP cooling tower shall be included in the operation record of cooling tower to accumulate maintenance and management data and serve as the technical basis for maintenance and improvement of cooling effect.

    faq02

    The selection of outdoor conversion temperature point of cooling tower cooling mode is directly related to the cooling hours of the system. It is assumed that the required water supply humidity at the end of the air conditioner is 12.7 ℃ through calculation. Considering the cooling range of the cooling tower, the heat loss of the pipeline and the heat exchanger to increase the water temperature by 4.5 ℃, the cooling tower cooling mode can be switched when the outdoor wet bulb temperature is equal to or lower than 8.2 ℃. After the cooling tower in the system is selected according to the cooling load in summer and the outdoor calculated wet bulb temperature in summer, its cooling capacity under the cooling tower cooling mode shall also be checked. Plate heat exchanger shall be selected as heat exchanger in indirect cooling system. Compared with the traditional shell and tube heat exchanger, the plate heat exchanger has high efficiency. Considering the specific outdoor wet bulb temperature and building load, the cooling amplitude of the cooling tower (the difference between the outlet temperature of the cooling tower and the outdoor wet bulb temperature) decreases with the increase of the size of the cooling filler. Therefore, for multiple sets of cooling tower systems, the method of series cooling tower can be used to increase the cooling effect and improve the outdoor conversion temperature of cooling tower cooling mode, so as to increase the cooling hours. In terms of circulating water equipment management, cooling tower fans account for a large proportion in terms of equipment quantity, maintenance workload and power consumption. The drenching packing of the cross flow cooling tower shall have a contraction inclination to the vertical central axis of the tower from the top to the bottom. The shrinkage angle of drip type water spraying filler should be 9 ° ~ 11 °; The contraction angle of the film type water spraying packing should be 5 ° ~ 6 °, and the cross flow cooling tower should be provided with measures to prevent short-circuit flow of air from the bottom of the packing to the water surface. After the cooling tower packing in the system is selected according to the cooling load in summer and the outdoor calculated wet bulb temperature in summer, its cooling capacity under the cooling tower cooling mode shall also be checked. The chilled water pump in the cooling water loop shall be provided with bypass. When the cooling tower is in the cooling mode, the chilled water pump is closed and the cooling water passes through the chilled water pump. At this time, the circulating water power is provided by the cooling water pump. Therefore, the conversion of special pumps for cooling should be considered in the system design.